electronic_controllers
 

Electronic Controllers and Indicators

ELECTRONIC CONTROLLERS AND INDICATORS. All-electronic indicating, alarm/control and annunciating instruments designed for superior visibility, accuracy and ease of installation.

Documentsdownload
V Electronic Controllers and Indicators
 

Description:

General Features


  • Display and alarm circuitry independent of one another.
  • Plug in replaceability.
  • Low power drain, noise immunity, cool running owing to C-MOS circuitry.
  • High resolution accuracy.
  • High ±0.5% resolution, accuracy of over ±1.0%. High reliability.
  • Optically-isolated inputs.
  • Simplified, one man installation with easy-locking swing-up catches.
  • Front replaceable display and scales.

Specifications Common to All Models


Parameter

Specifications at Room Temperature and Rated Voltage

Scale Length
inches(mm)

4.0(101.6)

Accuracy
(% of Span)

1%

Reolution
(% of span)

.5%

Response Time

.5 seconds nominal full scale repsonse of indicator. Adjustable to 3.0 secs.

Input Imedance

Current input DC and AC 300 mV maximum drop. Voltage input 25,000 ohms per volt minimum below 40V.
1 Megohm for 40V and greater.
Thermocouple Input- 100,000 ohms min for 10mV input.

Minimum Spans

DC Voltage- 8mV
AC Voltage- 100mV
DC Current- 25 microA
AC Current- 25 microA at 500 ohms.
Thermocouple- 8mV
RTD or termistor- 3 ohms change at 5 mA.

Maximum Self-Contained Spans

Current 500 MADC 5 AAC
Voltage 300 VDC 150 VAC

Input Power

Standard 120V±10% 50/60 Hz 14 VA max.
Optional 220V±10% 50/60 Hz 14 VA max.

Weight

4 pounds (1.8 Kg)

Connections

Standard-Barrier Stip (Optional-Multipin Connector)

Line Voltage Effect

<---- 0.05% per 1% of line change---->

Temperate Coefficient

<---- 0.03% per °C ---->

Operating Temperature

<---- °0C to °50C---->

Storage Temperature

<---- -°20C to °70C---->

Seismic

<----Designed to meet seismic requirements of nuclear power industry---->

Power "ON" indicator

<---- First Bar always lighted---->

Set Point Marker

<---- Double brightness bar---->

Alarm or Control Options

Accuracy

±1/2% of span. ± one segment

Dead Band

1% of span

Output Contacts

Model 9270: DPDT 5A at 120 VAC or 28 VDC resistive load.
Model 9270S: DPDT 1A at 120 VAC or 2A 28 VDC resistive load.